Life cycle cost and carbon footprint analysis of CuO–Al2O3/water hybrid nanofluids in thermoelectric vaccine refrigerators
Özet
This study investigates the application of a CuO–Al2O3/water hybrid nanofluid as a coolant in thermoelectric vaccine refrigerators, aiming to enhance heat dissipation from the Peltier module’s hot side. A 35-L cooling cabinet was utilised, and experimental comparisons were made using water and a 2% CuO–Al2O3/water hybrid nanofluid. Results show that the vaccine cabinet reaches the target temperature of 4 °C in 990 s with nanofluid, compared to 1200 s with water. The system’s energy consumption was reduced by 18.3%, and carbon emissions decreased by 12.3% over a 15-year lifespan, highlighting its environmental benefits. Despite similar coefficients of performance (COP), the nanofluid system demonstrates enhanced efficiency, shorter cooling times, and long-term sustainability advantages. These findings support the adoption of hybrid nanofluids in thermoelectric cooling applications for energy-efficient and environmentally friendly refrigeration systems.
Anahtar Kelimeler
- Scopus
- 6
- WoS
- 6
- OpenAlex
- 8
Tam Kayıt
| Alan | Değer | Dil |
|---|---|---|
| dc.contributor.author | Cuce, Pinar Mert | |
| dc.contributor.author | Guclu, Tamer | |
| dc.contributor.author | Cuce, Erdem | |
| dc.date.accessioned | 2026-10-29T19:09:57.448919561Z | |
| dc.date.available | 2026-10-29T19:09:57.448919561Z | |
| dc.date.issued | 2025 | |
| dc.description.abstract | This study investigates the application of a CuO–Al2O3/water hybrid nanofluid as a coolant in thermoelectric vaccine refrigerators, aiming to enhance heat dissipation from the Peltier module’s hot side. A 35-L cooling cabinet was utilised, and experimental comparisons were made using water and a 2% CuO–Al2O3/water hybrid nanofluid. Results show that the vaccine cabinet reaches the target temperature of 4 °C in 990 s with nanofluid, compared to 1200 s with water. The system’s energy consumption was reduced by 18.3%, and carbon emissions decreased by 12.3% over a 15-year lifespan, highlighting its environmental benefits. Despite similar coefficients of performance (COP), the nanofluid system demonstrates enhanced efficiency, shorter cooling times, and long-term sustainability advantages. These findings support the adoption of hybrid nanofluids in thermoelectric cooling applications for energy-efficient and environmentally friendly refrigeration systems. | |
| dc.description.sponsorship | Türkiye Bilimsel ve Teknolojik Araştırma Kurumu, TUBITAK | |
| dc.identifier.doi | 10.1007/s10973-025-14361-y | |
| dc.identifier.eissn | 1588-2926 | |
| dc.identifier.endpage | 10608 | |
| dc.identifier.issn | 1388-6150 | |
| dc.identifier.issue | 13 | |
| dc.identifier.scopus | 2-s2.0-105007244990 | |
| dc.identifier.startpage | 10595 | |
| dc.identifier.uri | https://rdlopen.rawdatalibrary.net/r/bayburt/12729 | |
| dc.identifier.volume | 150 | |
| dc.identifier.wos | WOS:001501658100001 | |
| dc.language.iso | en | |
| dc.publisher | Springer Science and Business Media B.V. | |
| dc.relation.ispartof | Journal of Thermal Analysis and Calorimetry | |
| dc.rights | info:eu-repo/semantics/openAccess | |
| dc.subject | Carbon footprint reduction | |
| dc.subject | CuO–Al<sub>2</sub>O<sub>3</sub> hybrid nanofluid | |
| dc.subject | Life cycle cost analysis (LCCA) | |
| dc.subject | Thermoelectric cooling | |
| dc.subject | Vaccine refrigeration | |
| dc.subject.classification | Thermodynamics | |
| dc.subject.classification | Chemistry, Analytical | |
| dc.subject.classification | Chemistry, Physical | |
| dc.subject.classification | Chemistry | |
| dc.subject.other | Carbon footprint | |
| dc.subject.other | Chilling | |
| dc.subject.other | Cooling towers | |
| dc.subject.other | Refrigerators | |
| dc.subject.other | Thermoelectric equipment | |
| dc.subject.other | Water cooling systems | |
| dc.subject.other | Carbon footprint reductions | |
| dc.subject.other | CuO–al2O3 hybrid nanofluid | |
| dc.subject.other | Footprint analysis | |
| dc.subject.other | Hybrid nanofluid | |
| dc.subject.other | Life cycle cost analyze | |
| dc.subject.other | Life cycle costs analysis | |
| dc.subject.other | Nanofluids | |
| dc.subject.other | Thermoelectric | |
| dc.subject.other | Thermoelectric cooling | |
| dc.subject.other | Vaccine refrigeration | |
| dc.subject.other | Thermoelectric refrigeration | |
| dc.title | Life cycle cost and carbon footprint analysis of CuO–Al2O3/water hybrid nanofluids in thermoelectric vaccine refrigerators | |
| dc.type | Article | |
| rdl.citation.openalex | 8 | |
| rdl.citation.scopus | 6 | |
| rdl.citation.wos | 6 | |
| rdl.oa.status | hybrid | |
| rdl.oa.url | https://link.springer.com/content/pdf/10.1007/s10973-025-14361-y.pdf | |
| rdl.scopus.quartile | Q2 | |
| rdl.sdg | SDG07 | |
| rdl.sdg | SDG12 | |
| rdl.sdg | SDG13 | |
| rdl.source.index | SCOPUS | |
| rdl.source.index | WOS | |
| rdl.wos.index | Science Citation Index Expanded (SCI-EXPANDED) |